This system comes with Free Heat Strips up to 10 kw Heat W/O Breaker for Free!!


Standard Features
• Energy-efficient compressor
• Single-speed condenser fan motor
• Factory-installed filter drier
• Copper tube/aluminum fin coil
• Service valves with sweat connections
and easy-access gauge ports
• Contactor with lug connection
• Ground lug connection
• AHRI Certified; ETL Listed


Cabinet Features
• Heavy-gauge galvanized-steel cabinet with a louvered sound control top
• Attractive Architectural Gray powder-paint finish with 500-hour salt-spray approval
• Steel louver coil guard
• Top and side maintenance access
• Single-panel access to controls with space
provided for field-installed accessories
• When properly anchored, meets the 2010 Florida
Building Code unit integrity requirements for hurri-
cane-type winds (Anchor bracket kits available.)

 

  GSX140241
Capacities  
Max Cooling (BTU/h) 24,000
SEER/EER 14 / 12
Decibels 74
Compressor  
RLA 7.7
LRA 38.0
Condenser Fan Motor  
Hp 1/8
FLA 0.7
Refrigeration System  
Refrigerant Line Size ¹  
Liquid Line Size (“O.D.) ⅜"
Suction Line Size (“O.D.) ¾"
Refrigerant Connection Size  
Liquid Valve Size (“O.D.) ⅜"
Suction Valve Size (“O.D.) ² ³ ¾"
Valve Type Sweat
Charge 72
Included piston: 0.057
Electrical Data  
Voltage-Phase (60 Hz) 208/230-1
Minimum Circuit Ampacity ⁴ 10.3
Max. Overcurrent Protection ⁵ 15 amps
Min/Max Volts 197/253
Conduit ½" or ¾"
Equipment Weight 126
Shipping Weight 141

 

Product Features
• Check flowrator for cooling and heat pump applications
• Direct drive, multi-speed PSC blower motor
• All-aluminum evaporator coil
• Coil mounting track for quick repositioning
• Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193
• Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193
• AHRI certified; ETL listed
• Rigid SmartFrame™ cabinet
• Horizontal or vertical configuration capabilities
• 21" depth for easier attic access
• DecaBDE-free thermoplastic drain pan with secondary drain connections
• Screw-less sides and back helps to reduce condensation when installed in humid locations
• Foil-faced insulation covers the internal casing to reduce cabinet condensation
• Galvanized, leather grain-embossed finish
• Glue-less cabinet insulation retention
• Tool-less filter access
• Field Installed 3 kW – 25 kW electric heater kits available

 

 

  ARUF29B14
Nominal Ratings  
Cooling (Btu/h) 25,000
Piston Size 0.057
Blower  
Diameter 9½"
Width 6"
Coil Connections  
Liquid ⅜"
Suction ¾"
Coil Drain Connect (FPT) ¾"
Electrical Data  
Voltage 208/230
Min Circuit Ampacity 2.2/2.2
Max. Overcurrent Device (Amps) 15/15
Minimum VAC 197
Maximum VAC 253
Blower Motor  
Full Load Amps (FLA) 1.75
Horsepower (HP)
Ship Weight (Lbs.) 100